GoodProx GP-RM-EM3040 Digital Earth Resistance Tester
|
|
Product Function
|
|
2-wire method and 3-wire method earth resistance measurement, earth voltage measurement, AC and DC voltage measurement.
|
|
Product features
|
|
1. The tester body is light, easy to carry and operate.
|
|
2. With the function of judgement the auxiliary grounding stake, the tester can display the resistance value of the auxiliary grounding stake in testing, which can avoid the error caused by the excessive earth resistance of the auxiliary ground stake.
|
|
3. With line resistance calibration function, which can avoid the error caused by the bad contact of the test line.It makes the measurement of low earth resistance more accurate and reliable in the site.
|
|
4. Earth voltage measurement function.
|
|
Technical Specification
|
|
Power Supply
|
DC9V, Alkaline dry battery (LR6 1.5VX6PCS)
|
|
Measurement Method
|
Earth resistance: rated current change-pole method, test current 20mA Max; Voltage to earth: average value rectification method
|
|
Earth Resistance Measurement
|
Range: 0.01Ω~2000Ω
|
|
Resolution: 0.01Ω
|
|
Accuracy: ±2%rdg±3dgt
|
|
Earth Voltage Measurement
|
Range: 0V~300V AC/DC
|
|
Resolution: 1V
|
|
Accuracy: ±2%rdg±3dgt
|
|
LCD Display
|
LCD display area: 58mmX46mm
|
|
Tester Dimension
|
183mm(L)X89mm(W)X56mm(H)
|
|
Weight
|
Total weight: about 2.37kg (include accessories)
|
|
Test Indicator
|
TESTING indicator light up, indicate that earth resistance is testing
|
|
Auxiliary Grounding Alarm
|
R P (s) R C (H) OK indicator light up, avoid errors caused by excessive grounding resistance of the auxiliary grounding electrode.
|
|
AC/ DC Voltage Alarm
|
When the voltage is greater than 36V, the Live circuit indicator light will flash and the buzzer will sound an alarm.
|
|
Line Resistance Calibration
|
Avoid errors caused by the test line not fully inserted into the tester interface or poor contact or the user replaces the lengthened test line, ensure earth resistance measurement accurate
|
|
Measurement Time
|
Earth resistance: 5 seconds/time;Voltage to earth: 2 times/second;
|
|
Automatic Shutdown
|
10 minutes without any operation after starting up, the tester will shutdown automatically
|
|
Battery Voltage
|
While battery voltage drop to around 7.2V, low battery voltage symbol“ ” will flash display, and remind to replace the battery
|
|
Overload Protection
|
Earth resistance: between each interfaces of E-P,E-C is AC 280V/3 seconds
|
|
Electromagnetic Property
|
IEC61010-4-3, wireless frequency electromagnetic field≤1V/m
|
|
Working Curren
|
Backlight: 56mA Max; Standby: 20mA Max(Backlight off); Measurement: 200mA Max(Backlight off)
|
|
Accessories
|
Tester:1PCS; Ground stake: 2PCS; Test line: 3PCS; Simple test line:1PCS; Tool bag:1PCS; LR6 battery: 6PCS
|
|
Warranty
|
12 Months
|